  "id": 22,
  "title": "SGK Integrated-magnetics Transformers",
  "family": "Integrated-magnetics Transformers",
  "description": "Transformer and reactor functions combined on a shared magnetic core for UPS, metro traction and related power conversion applications.",
  "sections": [
    {
      "heading": "Overview",
      "paragraphs": [
        "Brochure states that integrating transformer and reactor magnetics increases power density and efficiency, reduces output ripple and improves transient output response, while reducing primary inverter-switch losses and magnetic-component size and losses.",
        "Magnetic integration combines two or more discrete magnetics (DM) on one magnetic core. Coupling and parameter design support integration and miniaturization; fewer connection points reduce terminal losses in high-current circuits."
      ]
    },
    {
      "heading": "Design and performance",
      "paragraphs": [
        "Brochure states that customer-specified short-circuit impedance is available, normally 5%–30%, for isolation or autotransformer designs, single-phase or three-phase. Leakage-inductance calculation determines main and auxiliary core cross sections, auxiliary-core air gaps, temperature rise and size. A foil-winding machine is customized for double-core transformer windings."
      ]
    },
    {
      "heading": "Principle",
      "paragraphs": [
        "The principle diagram combines a discrete series inductance L and transformer T into an integrated T+L magnetic assembly; either arrangement of L relative to T is illustrated. Integrated filtering inductance with specified short-circuit impedance is offered for 1 kVA–1000 kVA."
      ]
    }
  ],
  "specifications": [
    [
      "Custom capacity range",
      "1–1000 kVA"
    ],
    [
      "Typical short-circuit impedance",
      "5%–30%"
    ]
  ],
  "models": [
    {
      "designation": "SGK-2",
      "values": [
        "3",
        "80",
        "50",
        "380",
        "615",
        "280",
        "400",
        "590",
        "14×20",
        "H"
      ]
    },
    {
      "designation": "SGK-2",
      "values": [
        "3",
        "100",
        "50",
        "400",
        "735",
        "400",
        "460",
        "580",
        "14×20",
        "H"
      ]
    }
  ],
  "tables": [
    {
      "caption": "Parameters and dimensions",
      "columns": [
        "Model",
        "Phases",
        "Rated capacity (kVA)",
        "Frequency (Hz)",
        "A (mm)",
        "B (mm)",
        "C (mm)",
        "D (mm)",
        "E (mm)",
        "Mounting hole (mm)",
        "Insulation class"
      ],
      "rows": [
        [
          "SGK-2",
          "3",
          "80",
          "50",
          "380",
          "615",
          "280",
          "400",
          "590",
          "14×20",
          "H"
        ],
        [
          "SGK-2",
          "3",
          "100",
          "50",
          "400",
          "735",
          "400",
          "460",
          "580",
          "14×20",
          "H"
        ]
      ]
    }
  ],
  "notes": [
    "Both table rows use the original designation SGK-2; capacity distinguishes the variants. Special specifications and dimensions can be manufactured to customer requirements."
  ],
  "slug": "sgk-integrated-magnetics-transformers",
  "category": "industrial-transformers",
  "categoryTitle": "Industrial Transformers",
  "relatedCategories": [],
  "image": "/catalog/products/sgk-integrated-magnetics-transformers.webp",
  "href": "/products/series/sgk-integrated-magnetics-transformers",
  "pdfPage": 14,
  "side": "right",
  "sheet": "/catalog/sheets/14-right.webp",
  "sheetWidth": 1007,
  "sheetHeight": 1375
}