Application scope
Used in electronics, industrial and mining enterprises, machine tools and mechanical equipment for general control circuits, safety lighting and indicator-lamp supplies.
Get a quote ↗JIADEST / Safety Lighting Transformers
Manufacturer’s series: JMB
50–60 Hz transformers for control circuits, safety lighting and indicator lamps.
Search the complete technical catalog ↗
Used in electronics, industrial and mining enterprises, machine tools and mechanical equipment for general control circuits, safety lighting and indicator-lamp supplies.
J: local; M: lighting; B: transformer; suffix: rated capacity in VA.
Primary and secondary windings are wound separately. If only one secondary winding is provided, it carries the full rated transformer capacity. Where control, lighting and indicator windings are combined, each is wound according to its allocated capacity.
For a single tapped secondary winding, intermediate taps have capacities lower than the transformer rating. Only the highest-voltage output terminals can carry full rated capacity.
Altitude not exceeding 2500 m. Ambient air temperature from -25°C to +40°C. The maximum mean relative humidity in the wettest month is 90%.
Install where there is no severe vibration or impact, no explosive atmosphere, and no gases or conductive dust sufficient to corrode metal or damage insulation.
The brochure’s sixth environmental condition reads “locations exposed to rain and snow”; this original wording is retained and requires confirmation against the supplied enclosure rating.
| Rating (VA) | Rated input (V) | Rated output (V) | Overall dimensions (mm) |
|---|---|---|---|
| 25 | 220 | 6 | 150×160×130 |
| 50 | 220 | (6.3) | 150×160×130 |
| 100 | 220 | 12 | 150×160×130 |
| 150 | 220 | 24 | 160×170×135 |
| 200 | 220 | 36.48 | 160×170×135 |
| 250 | 200 | 110 | 180×170×155 |
| 300 | 380 | 127 | 180×170×155 |
| 400 | 380 | 220 | 210×230×175 |
| 500 | 380 | (330) | 210×230×175; 200×175×175 |
| 700 | 220 | 6 | 218×290×185 |
| 1000 | 220 | (6.3) | 218×290×185; 210×230×185 |
| 1500 | 220 | 12 | 260×290×235 |
| 2000 | 220 | 24 | 260×290×235; 240×240×225 |
| 2500 | 220 | 36.48 | 280×350×230 |
| 3000 | 220 | 110 | 280×350×230; 250×300×240 |
| 4000 | 380 | 127 | 360×355×280 |
| 5000 | 380 | 220 | 360×355×280; 350×290×285 |
| 10K | 380 | (330) | 510×430×490 |