Transformer manufacturing. Global supply.
Qingdao, China
◎ English⌄
EnglishSpanishComing soonPortugueseComing soonFrenchComing soonRussianComing soonItalianComing soonGermanComing soonDutchComing soonArabicComing soonKoreanComing soonJapaneseComing soonHindiComing soonThaiComing soonTurkishComing soonVietnameseComing soonIndonesianComing soon

JIADEST / Specialty & Test Transformers

Triple-Frequency Test Transformers

Manufacturer’s series: SBF

Saturated-core frequency-triplers for induced overvoltage testing, converting 50Hz to 150Hz.

Search the complete technical catalog ↗
Triple-Frequency Test Transformers product photograph
Open reference photograph ↗
Product reference photograph. Refer to the technical tables and drawings for each configuration.

Overview

Magnetic saturation extracts the third harmonic, described as the largest harmonic component, to supply interturn, inter-section and interlayer increased-frequency/increased-voltage tests of inductive-winding electrical products. The purpose is to assess winding insulation strength and withstand level.

Construction and magnetic principle

A three-core five-limb structure operates above saturation flux density. In the open-delta-connected secondary, the vector sum of fundamental-frequency positive-sequence EMFs is zero; the open terminals provide in-phase 150Hz third-harmonic zero-sequence voltage.

The brochure includes three-phase frequency-tripler circuit and transformer connection diagrams.

Technical specifications.

ParameterPublished specification
InputThree-phase 380V, 50Hz
Output range 150–500V (maximum 750V), 150Hz
Output range 2100–1000V (maximum 1500V), 150Hz
Capacity range1–1000KVA
WaveformSine wave; distortion below 1[%]
Load typesResistive, inductive or capacitive

Models & configurations.

Designations are retained as published. Separate rows or variants with the same designation remain distinct in the relevant tables.

  • SBF-3/500380 · 0–500 · 3
  • SBF-5/500380 · 0–500 · 5
  • SBF-10/500380 · 0–500 · 10
  • SBF-15/500380 · 0–500 · 15
  • SBF-20/500380 · 0–500 · 20
  • SBF-5/1000380 · 0–1000 · 5
  • SBF-10/1000380 · 0–1000 · 10
  • SBF-20/1000380 · 0–1000 · 20
  • SBF-50/1000380 · 0–1000 · 50

Typical SBF model parameters

Typical SBF model parameters
ModelInput voltage (V)Output voltage (V)Capacity (KVA)
SBF-3/5003800–5003
SBF-5/5003800–5005
SBF-10/5003800–50010
SBF-15/5003800–50015
SBF-20/5003800–50020
SBF-5/10003800–10005
SBF-10/10003800–100010
SBF-20/10003800–100020
SBF-50/10003800–100050

DIMENSIONS / CONNECTIONS / SOURCE DATA

Technical information and original product sheets.

The original sheet retains all dimensioned drawings, connection diagrams, table footnotes and published values. It is supplied in its original language for direct verification against the English specification.

Open original sheet at native resolution ↗
View complete original technical sheet (Chinese)Original technical sheet with complete specifications and dimension drawings for Triple-Frequency Test Transformers

TALK TO JIADEST

Discuss your Specialty & Test Transformers requirements.

Use the exact model, voltage, current or power rating, duty cycle and drawing reference when requesting a quotation. Confirm source discrepancies and project-specific requirements in the approved technical agreement.

Request a quotation ↗
JIADEST / LET’S TALK POWER

Planning a power project?

Share your requirements when you’re ready. Our team can help with equipment selection.

Need to share more? Use the detailed inquiry form ↗